Zone heating controller ZCE6 Basic

ZCE basic controllers are designed to regulate zone heating and/or cooling. The control is carried out by means of thermo actuators on the manifold valves based on reference temperatures obtained from the room units. Six separate temperature zones are available with the possibility of controlling a total of 14 circuits.

Use

  • regulating the underfloor heating or cooling system,
  • regulating a wall or ceiling heating or cooling system,
  • regulating a convector heating or cooling system.


PERFORMANCE COMPARISON ZCE6
Basic
ZCE6
Forward
REGULATING HEATING CIRCUITS
Control of the riser temperature constant Yes
Weather-controlled riser temperature control Yes
REGULATING THE ENERGY SOURCE
Switching the source on/off Yes
USER FUNCTIONS
Space heating or cooling according to a timed programme Yes Yes
Automatic winter/summer switchover Yes Yes
The PARTY function – simple extension of comfort heating Yes Yes
ECO function – activating energy-saving mode Yes Yes
HOLIDAY function – activating holiday mode Yes Yes
Emergency operation in case of loss of communication with the room unit Yes Yes
HEATING SYSTEM PROTECTION
Protection against room freezing Yes Yes
Protection against overheating of rooms Yes Yes
Periodic start-up of thermal drives during inactive periods Yes Yes
Periodic start-up of pump and mixing valve during inactive period Yes
DISPLAY OF DATA
LED indication of temperature zone operation Yes Yes
LED indication of circulation pump operation Yes
LED indication of power source operation Yes
LED indication of mixing valve operation Yes
LED indication Bus connection Yes Yes
REMOTE ACCESS
USB connection to PC Yes Yes
SET-UP AND INSTALLATION
Mounting on a mounting rail Yes Yes
Easy installation and connection Yes Yes
USE
Controlling the underfloor heating or cooling system Yes Yes
Controlling a wall or ceiling heating or cooling system Yes Yes
Controlling a convector heating or cooling system Yes Yes
TECHNICAL CHARACTERISTICS
Control of 6 independent temperature zones Yes Yes
Choice of voltage for 24 VAC or 230 VAC thermal actuators Yes Yes
By connecting an antenna, wired or wireless room units, or a combination of both, can be connected to the controller Yes Yes
Silent control of thermal actuators with electronic relays Yes Yes
Maximum number of room units 6 6
Circulation pump control Yes
Inlet temperature control with mixing valve Yes
The possibility of combining temperature zones into a larger and single zone. Yes Yes
Possibility to regulate the energy source No Yes
Number of inputs for temperature sensors 3 3
Number of digital inputs 3 3
Number of analogue outputs 1 1
Number of exits (zones/other exits) 6/0 6/4
Max. number of controllers in a BUS link 6 6
REGULATING HEATING SYSTEMS
Controlling the underfloor heating or cooling system Yes Yes
Controlling a wall or ceiling heating or cooling system Yes Yes
Controlling a convector heating or cooling system Yes Yes

Key features of the ZCE6 Basic zone heating controller

  • up to 3 preset hydraulic schemes,
  • control of 6 independent temperature zones,
  • choice of supply voltage for the thermal actuators 24 VAC or 230 VAC,
  • by connecting an antenna, wireless room units can be connected to the controller, including a combination of wired and wireless room units,
  • inaudible control of thermal actuators with electronic relays,
  • the possibility of combining temperature zones into a larger, single zone,
  • the possibility to BUS-connect multiple controllers.


TECHNICAL DATA ZCE 6 Basic
Weekly programme hour Yes
Connection voltage 230 V ~ , 50 Hz
Own consumption 5 W
Standby power consumption Maximum 0,5 W
Number of entrances 3 x temperature sensor (Pt 1000)
3 x digital input
Number of outputs 6 x electronic relay for zone control
Relay outputs 4 (1) A ~, 230 V ~
Triac output 1 (1) A ~, 230 V ~
Clock power supply Battery R1025 (Li-Mn) 3 V
Watch accuracy +/- 1 s (24 h) at 20 °C
Degree of protection IP20 to EN 60529
Safety class I according to EN 60730-1
Type of operation 1B to EN 60730-1
Type of temperature sensors Pt1000
Type of operation PI regulator
Housing material PC+ABS – termoplast
Permissible ambient temperature 5 ÷ 40 °C
Storage temperature -20°C to +65°C
Mass 360 g
Number of pieces per packing unit 6 pieces
Dimensions (W × H × D): 233 x 73 x 41mm

Electrical connection