Constant Temperature Controllers SCC40
Constant temperature controller SCC40

Constant temperature controller SCC40

The SCC40 Constant Temperature Controller is used to control the return temperature of solid fuel boilers, to fill the heat storage tank...

Use

  • For regulating the return temperature of solid fuel boilers.
  • Filling up heat storage tanks.
  • Control of a pellet or combi boiler.

Key features of the SCC40 constant temperature controller

  • Adjustable return temperature.
  • Boiler overheating protection.
  • Graphical display of temperatures by day for the last week.
  • Measurement and display of the energy generated.
  • Diagnostics only, with fault warning and notification when temperatures are exceeded.
  • 6 preset hydraulic schemes.
  • Two-stage filling of the feeder.
  • Up to 3 unused outputs can be freely programmed.
  • Possibility to adjust the mixing valve according to the temperature of the pipeline and the source.
  • Pump control depending on pipeline and source temperature.
  • Simulation of system operation.
COMPARING THE PERFORMANCE OF CONTROLLERSSCC30SCC40
USE
For regulating the return temperature of solid fuel boilersYesYes
Filling storage tanksYesYes
Pellet or combi boiler controlYesYes
TECHNICAL CHARACTERISTICS
Number of preset hydraulic schemes26
Number of storage tanks12
Number of mechanical relays24
Number of electronic relays22
Number of inputs for temperature sensors77
Additional sensor for source temperature measurementYesYes
Possibility to adjust the mixing valve according to the pipeline and source temperatureYesYes
Possibility to regulate the pump according to the pipeline and source temperatureYesYes
Measuring the energy generated (kW/h)YesYes
Flow measurement option with pulse meter (l/min)YesYes
Free programming option1 exitup to 3 outputs
REGULATING SYSTEMS
One-step filling of the feederNoYes
Two-stage filling of the feederNoYes
REGULATING HEAT SOURCES
Pellet boilerYesYes
HEATING SYSTEM PROTECTION
Boiler overheating protectionYesYes
Anti-blocking function for pumpsYesYes
Anti-blocking function for pumps and diverter valvesNoYes
A COMPREHENSIVE OVERVIEW OF THE HEATING SYSTEM'S OPERATION
Graphical display of temperatures by day for the last weekYesYes
Detailed display of temperatures for the current dayYesYes
Notifications of activated safety functions and system fault warningsYesYes
Possibility to simulate sensors and analyse system performanceYesYes
REMOTE ACCESS
USB connection to a PCYesYes
SET-UP AND INSTALLATION
Wizard for easy and fast device start-upYesYes
13 language user interface EN, DE, FR, NL, PL, ES, SL, IT, CS, LT, GR, HU, HRYesYes
Setting the operation by selecting the hydraulic schemeYesYes
"Help" key for quick help with settingsYesYes
Graphically configurable time programmesYesYes
Possibility to simulate system operationYesYes
Logging and displaying changes to settingsYesYes
Basic settings can be retrieved in case of loss or unwanted changesYesYes
Possibility to programme free outputsYesYes
Wall or DIN-rail mountableYesYes
Easy installation and connectionYesYes
TECHNICAL DATASCC40
Illuminated graphic displayYes
Operating hours counterYes
Programme clockYes
Connection voltage230 V ~, 50 Hz
Energy consumption2,5 W
Standby power consumptionMaximum 0,5 W
Number of entrances7 x temperature sensor (Pt 1000)
1 x pulse input
Number of outputs2 x triac (R2, R3)
4 x relays ( R1,R4 R5, 56)
Relay outputs4 (1) A ~, 230 V ~
Triac outputs1 (1) A ~, 230 V ~
Clock power supplyBattery CR2032 (Li-Mn) 3 V
Time display accuracy+/- 1 s (24 h) at 20 °C
Degree of protectionAnd after P20 / EN60529
Safety classI according to EN 60730-1
Type of operation1B to EN 60730-1
Type of temperature sensorsPt1000 or KTY10
Housing materialASA - thermoplastic
Operating temperature 5÷40 °C
Storage temperature-20÷65 °C
Product weight410 g
Number of pieces per packing unit6 pieces
Dimensions (W × H × D): 113 x 163 x 48 mm


Electrical connection


We offer

  • Purchase advice and free home viewing.
  • Assistance in obtaining grants from the ECO-FUND.
  • A wide network of verified, professionally trained installers and technicians throughout Slovenia.

Please send us a brief description of what you are interested in and your details. We will contact you and work with you to find the right solution.

Click or drag files to this area to upload.You can upload up to 3 files.
Allowed files: jpg, png, pdf, doc, xls

NOTICE

The Seltron service will be closed from 27 December to 29 December 2023.
Any emergencies or issues that arise during our absence will be dealt with as soon as the service reopens on 3 January 2024.
Thank you for your understanding.

Opening hours of the Seltron store on 30 December 2023.
  • from 7.00 to 12.00